Transmission Line Sequence Network Diagram
Free Printable Transmission Line Sequence Network Diagram
Figure 8 shows the one line diagram of a generator g feeding a motor m through a two section transmission line.
Transmission line sequence network diagram. Z1 z2 j?? l m 41 z0 j?? l 2m 42 so in analysis of networks with transmission lines it is now possible to replace the lines with three independent single phase networks. To calculate the sequence voltage changes throughout the pps nps and zps sequence networks using their nodal impedance matrices we need to calculate the equivalent sequence currents to be injected at nodes j and k in each sequence network. Assume that the base values in the region of transmission lines are 100mva 345kv. Gm l1 l2 r 0 figure 1 system one line diagram.
In figure 1 c s. Transmission line is bilateral an interconnected transmission network is not bilateral due to the dispersion of active components generators throughout the network. Because of a transmission line s passive and bilateral properties the phase sequence of the applied voltage makes no difference as b c positive sequence voltagesa. Using these complete sequence networks of a power system can be easily drawn.
Figure 1 single line diagram of transmission and distribution network. The voltage is then stepped up by suitable 3 phase transformers for transmission purposes. These are easily calculated from figure 6 24 by replacing each sequence voltage v x in series with the circuit impedance z x x p n or z with a. Central station where power is generated by 3 phase alternators.
The positive negative and zero sequence impedances of the balanced transmission line are then. Represents the central station where power is generated by 3 phase alternators at 6 6kv or 11kv or 13 2kv or even 32 kv. Neutral and or earth is so much greater than for positive and negative sequence currents which return balance. In fact the single line reactance diagram as employed for calculation of symmetrical fault current is the positive sequence diagram of the power system.
On the given bases the transmission line sequence reactances are x x 10 x 30. This is because the spacing between the go and return i e. Figure 9 shows the positive negative and zero sequence networks of the system. The zero sequence network must therefore have a path from the line h on the star side through the zero sequence impedance of the transformer to the reference bus while an open circuit must exist on the line l side of delta see fig.
The reactance of transmission lines of zero sequence currents can be about 3 to 5 times the positive sequence current the lighter value being for lines without earth wires. If the star neutral is. The generator is resistance grounded through resistor r0 while the motor remains ungrounded. The positive sequence network is drawn by examining one line diagram of the power system.